2.3 Input, Output and Memory Addressing

PLC applications interact with the external world through Input and Output modules and/or SCADA communication protocols. When designing your PLC applications, you decide which variables should be attached to I/O and communication modules by labeling the variable with a PLC address.

OpenPLC Runtime uses the IEC 61131-3 nomenclature to address input, output and memory locations. The addressing of I/O locations is done through the use of special character sequences. These sequences are a concatenation of the percent sign “%”, a location prefix, a size prefix and one or more natural numbers separated by blank spaces. The following location prefixes are supported:

  • I for input
  • Q for output
  • M for memory

The following size prefixes are supported:

  • X for bit (1 bit)
  • B for byte (8 bits)
  • W for word (16 bits)
  • D for double word (32 bits)
  • L for long word (64 bits)

For example, if you want to read the state of the first digital input into a BOOL variable, you must declare your variable located at: %IX0.0. If you want to write the contents of a UINT variable into the second analog output, you should declare your UINT variable located at %QW2.

Note: PLC to physical I/O mapping is platform dependent. For more information on PLC I/O mapping for every supported platform, check: 2.4 Physical Addressing

As you probably have noticed, bit (X) PLC addresses have a two-part hierarchical address. The least significant part (right-most) can be interpreted as a position in a byte and must be in the range 0 to 7. The most significant part (left-most) must be no more than 1023. Parts are separated by a single period. Data sizes other than X have a one-part hierarchical address. They must not contain a period (.) and must be no more than the maximum memory location address for your platform.

The following are invalid examples of PLC addresses in OpenPLC for the stated reason:

  • %IX0.8 The least significant index is greater than 7.
  • %QX0.0.1 Three part hierarchy is not permitted address.
  • %IB1.1 Two part hierarchy is only permitted for X data size.